Air cooled heat pump screw refrigeration unit YSPA
Classification:
key word:
Refrigeration unit
Inquiry
Detailed introduction
Air cooled screw unit is to meet the requirements of industrial installation environment, the refrigeration host, condensation radiator, evaporator, control system integrated skid, mainly used to install in the outdoor or the lack of cooling water.
Can be designed according to the process requirements; Frequency conversion compressor, frequency conversion fan, frequency conversion control system
Refrigerant R22 / R404 R410 / R407C/R507 R1270 < / p >
Normal temperature refrigeration unit :7℃/30, used in conventional heat exchanger cooling, equipment mold cooling, oil temperature control, synthetic reaction temperature control, etc.
Low temperature type :0℃ to -180℃, used in fine chemical reaction kettle temperature control, BOG liquefaction, LNG liquefaction, natural gas liquefaction, nitrogen liquefaction, etc. (non-standard separate count)
A, room temperature refrigeration unit
|
Model YSPA |
405HE |
520HE |
635HE |
775HE |
930HE |
1160HE |
1270HE |
1550HE |
|
Cooling capacity (KW) |
400 |
516 |
623 |
785 |
915 |
1139 |
1246 |
1570 |
|
Compressor Power (KW) |
98 |
130 |
156 |
191 |
228 |
260 |
313 |
383 |
|
Fan power (KW) |
14 |
18 |
22 |
29 |
32 |
39 |
43 |
57 |
|
Refrigeration conditions: chilled water inlet and outlet water temperature 12/7℃, water side heat exchanger fouling coefficient 0.018m².K/kW, outdoor temperature 35℃, power supply voltage: 380V/3Ph/50Hz; |
||||||||
Air cooled screw chiller Advantages :
1, do not need to occupy a special machine room, and do not need to install cooling tower and pump room, convenient operation, without professional maintenance;
2. Air cooled unit has no cooling water system, saving urban water; (The floating water loss of water cooling tower of water cooling unit is 5‰ per hour)
3. Lower maintenance cost than water cooling unit;
4, energy-saving operation (according to the actual load refrigeration load 12.5% to 100% stepless adjustment)
Disadvantages of air-cooled screw chiller;
1, generally installed in the outdoor, the operation environment is relatively harsh, in the maintenance and reliability are not as convenient as water cooled chiller;
2. The high condensing temperature reduces the operating efficiency of the refrigeration unit;
3. The high temperature refrigeration effect is poor in summer;
Previous
Previous
Related products
Consultation quotation
*Note: Please make sure to fill in the information accurately and maintain smooth communication. We will contact you as soon as possible
National Service Hotline
Address: No. 66, Shuangfu 1st Road, Chenghua District, Chengdu
SAF Coolest v1.2 设置面板 APQSS-ASNW-NSZSE-AVQ
无数据提示
Sorry,There is currently no content in the current column!
You can view other columns or return to Home